Industrial boiler
Steam Accumulator for Peak Load Shaving
Steam accumulator, 5-80 m³, storing flash steam at 1.0-2.5 MPa so a boiler can run at steady load through sharp demand peaks.
View detailsShell-and-tube heat exchanger, 10-250 m², in Q245R or Q345R with 304/316 tubes, for steam, hot water and process duties.


A shell-and-tube exchanger is a pressure vessel with a tube bundle inside it. One fluid flows through the tubes, the other through the shell across baffles that force it back and forth. The baffles support the tubes, keep the shell-side fluid moving across them rather than along them, and set the pressure drop. Change the baffle spacing and you change the heat transfer coefficient, the pressure drop and the vibration risk at the same time.
Three configurations cover most duties. The fixed tube sheet is the cheapest and handles clean fluids with a moderate temperature difference; the U-tube allows the bundle to be withdrawn and tolerates thermal expansion; the floating head allows both, at the cost of a more complex and more expensive shell. For steam-to-water duties with a 100 K approach, the fixed tube sheet is usually adequate; for oil cooling with a large temperature difference, the U-tube is the safer choice.
The design starts with the duty, the four terminal temperatures and the allowable pressure drop on each side. From those, the log mean temperature difference and the required area follow. Two margins are then applied: a fouling factor for each side, and a margin on area for the uncertainty in the correlations. Over-margining is as bad as under-margining — an exchanger with 50 per cent excess area will run with the control valve nearly closed, which causes hunting and uneven flow.
Counter-current flow gives the highest effectiveness for a given area, which is why most process exchangers are arranged that way. Where the terminal temperatures cross — the cold outlet above the hot outlet — a multi-pass arrangement is needed, and the correction factor must be checked rather than assumed.
The shell is normally Q245R for lower pressures and Q345R where the design pressure or the temperature requires thicker plate. Heads are elliptical, with the thickness calculated for the same design conditions and checked at the nozzle openings. Tube sheets are drilled and, where the service demands it, clad or solid stainless.
Tubes are 19×2 mm or 25×2.5 mm in 304 or 316 stainless, or in carbon steel where the water is treated and the duty is clean. The choice is a corrosion question, not a thermal one: 316 is worth the premium where chlorides are present or the water is aggressive, and carbon steel is fine in a closed, treated heating circuit.
Fouling is the largest uncertainty in any exchanger design. A fouling factor of 0.0002 m²K/W is reasonable for clean treated water, 0.0005 for river water, and considerably more for process streams with suspended solids. The designer applies the factor; the operator lives with the result, so the tube-side fluid should be the dirtier one wherever possible, because tubes are easier to clean than a shell.
Specify a tube diameter that will pass a brush, and provide removable headers or a bonnet with a drain so that the bundle can be flushed. Chemical cleaning in place is effective for scale, but it does nothing for hard deposits that need a brush, so the tube diameter should never be so small that a brush cannot pass.
To quote an exchanger we need: hot and cold fluid, flow rates, inlet and outlet temperatures, allowable pressure drop, design pressure and temperature, and the corrosiveness of both streams. From that we return a proposal with area, tube count, shell diameter, nozzle sizes and connection details.
Every unit is water-tested at 1.25 times design pressure on each side, with the tube-to-tube sheet joints examined for leakage. Welds are examined to the extent required by the design category, and the exchanger is documented against the D1/D2 licence before dispatch. Lead time is normally 25 to 45 days from approval of the drawings.
Put the hotter, cleaner fluid on the shell side where insulation is easier and pressure drop is lower, and the dirtier fluid through the tubes where it can be cleaned. If both are dirty, choose the side with the higher allowable pressure drop for the tube pass.
Yes. Steam on the shell side with water in the tubes is the standard district heating and process hot water arrangement. The shell must be designed for the steam pressure and fitted with a trap and air vent.
Inspect and clean according to the fouling trend, typically every one to three years. Watch the approach temperature: a rise of 3-5 K at constant flows is the signal that cleaning is due.
| Heat transfer area | 10 m² | 50 m² | 120 m² | 250 m² |
|---|---|---|---|---|
| Shell diameter | DN400 | DN600 | DN800 | DN1000 |
| Design pressure | 1.0 MPa | 1.0 MPa | 1.6 MPa | 1.6 MPa |
| Design temperature | 150 °C | 150 °C | 200 °C | 200 °C |
| Tube material | 304 stainless | 304 stainless | 316 stainless | 316 stainless |
| Tube size | 19×2 mm | 19×2 mm | 25×2.5 mm | 25×2.5 mm |
| Hydrostatic test | 1.25× design | 1.25× design | 1.25× design | 1.25× design |
External links open the publisher’s website and are provided for background reading.
Include the capacity (t/h or MW), fuel, working pressure and site country so the proposal matches your permit limits.
We appoint one or two partners per country to quote, deliver and service our boilers locally. Territory protection, factory pricing and commissioning support are part of the agreement.