Eight milligrams per litre, and what it does
Cold water in equilibrium with air holds about 8 mg/L of dissolved oxygen. At 8 mg/L, a 10 t/h feedwater flow carries 80 g of oxygen into the boiler every hour, nearly 2 kg a day. That oxygen does not stay dissolved. It comes out of solution at the hot metal surface, and in the presence of water and chloride it drives an electrochemical cell that eats steel in small, deep pits. A pit that starts on the water side of a tube or a shell plate grows under its own corrosion product, is invisible from outside, and reaches the wall thickness in two to five years.
This is the failure that a deaerator prevents, and it is why the specification matters less than the result. A tray deaerator, a spray deaerator and a vacuum deaerator all remove oxygen; they differ in how far they go, how much steam they use and what feedwater temperature they produce. Choosing between them on price alone is how plants end up with 100-200 ppb of residual oxygen and a tube failure in year four.
Temperature is the mechanism
Oxygen solubility falls steeply as water approaches its boiling point. At 20 °C it is 8 mg/L, at 60 °C about 4 mg/L, at 90 °C about 1.5 mg/L, and at 105 °C, the saturation temperature at 0.02 MPa gauge, it is effectively zero. A deaerator therefore does not scrub oxygen out with chemistry; it heats the water to saturation and gives the released gas a path to atmosphere. The vessel runs at 0.02-0.05 MPa gauge so that saturation sits at 104-105 °C, just above atmospheric boiling, which keeps air from leaking in and gives the vent a positive flow.
Reaching saturation is easy. Reaching it uniformly, in every droplet, at every load, is the engineering. Water falling through a spray loses its oxygen from the droplet surface, and the interior of a 1 mm droplet takes far longer to release its gas than the surface. That is why contact area and residence time, not steam flow, decide the residual figure.
Tray, spray and vacuum compared
A spray-only deaerator is a vessel with nozzles at the top and a steam space below. It is cheap, short and tolerant of dirt, but it struggles below about 100 ppb because the droplets are large and the contact time is short. It suits small plants where the boiler is a fire-tube unit at low pressure and the feedwater is mostly condensate.
A tray deaerator adds a stack of stainless trays below the sprays. Water cascades from tray to tray in thin films while steam rises counter-current, and the repeated re-mixing exposes fresh surface to the steam. A well-designed tray stack reaches 15 ppb or better with a steam consumption of 0.5-2% of the feedwater flow, and it holds that performance from 20% to 100% load. This is the standard choice for industrial steam plants above about 2 t/h.
A vacuum deaerator works below atmospheric pressure, so it can use low-grade heat at 40-60 °C and still boil the water. It suits hot-water systems and plants with no steam available, but it needs a vacuum pump, a water seal and more maintenance, and the residual oxygen is typically 50-100 ppb rather than 15.
Venting, chemistry and the part people close
The vent is the only exit for the oxygen and for the non-condensable gases that come in with the water. It must pass the released gas plus a small steam purge, typically 0.5-1% of the steam flow, and it must be visible. A vent that has been throttled shut because someone objected to the plume has turned the deaerator into an expensive feedwater heater: the oxygen has nowhere to go, the vessel pressure rises, and the residual oxygen climbs back towards saturation.
Mechanical deaeration stops at about 15 ppb. The remaining oxygen is handled by a chemical scavenger, typically sodium sulphite or a tannin blend, dosed into the storage section or the feed line. Sulphite adds dissolved solids, which matters on a high-cycle boiler; tannins and other volatile scavengers do not, but they cost more. The scavenger dose should be controlled on a measured residual, not on a fixed pump setting, because excess sulphite is a corrosion risk in its own right and a waste of chemical.
Sizing, NPSH and placement
Size the deaerator for the maximum evaporation plus blowdown, not the average. A 20 t/h SZS boiler at 5% blowdown needs 21 t/h, and the tray stack should be selected at that flow with the design steam flow stated. The storage section below the trays provides 5-25 m³, giving 5-15 minutes of feedwater buffer, which lets the level control ride through a sudden demand and gives the scavenger time to act.
The hydraulic detail that causes most commissioning problems is net positive suction head. Water at 105 °C is at saturation, so any pressure drop at the pump suction flashes it. The deaerator must sit 3-5 m above the feed pump, with a short, generously sized suction line and a minimum of fittings. A feed pump that cavitates at 105 °C is not a pump problem; it is a layout problem, and no amount of pump rebuilding will fix it.
Operating faults and the table
The common faults are worth recognising. Flooding at high load means the tray stack is undersized or the drain from the trays is restricted, and water carries into the steam space. Low outlet temperature means insufficient steam, a fouled tray stack or a vent that is too wide open. Oxygen spikes after a cold start are normal for the first hour and should not be chased with scavenger. Tray fouling from hardness carry-over is permanent damage: the trays are stainless precisely because they must not corrode, but they can still scale, and a scaled tray stack loses contact area and performance.
| Type | Residual oxygen | Outlet temperature | Heat source | Best application |
|---|---|---|---|---|
| Spray | 100-200 ppb | 104 °C | Low-pressure steam | Small fire-tube plants |
| Tray | ≤15 ppb | 104-105 °C | Low-pressure steam | Industrial steam above 2 t/h |
| Spray-tray combined | ≤15 ppb | 105 °C | Low-pressure steam | Variable load, dirty water |
| Vacuum | 50-100 ppb | 40-60 °C | Hot water or waste heat | Hot-water systems, no steam |
The economic case is straightforward. Heating feedwater from 20 °C to 105 °C absorbs about 355 kJ per kilogram, and every 6 °C of feedwater temperature is worth roughly 1% of fuel. A deaerator therefore pays for itself twice: once in the heat it recovers from steam that would otherwise be vented or throttled, and once in the tube and shell life it preserves. The second payment is the larger one, and it does not appear on any payback calculation until the first tube fails.
Selection should start with the required residual oxygen and the available heat source, then move to turndown, storage volume and NPSH. The type follows from those answers. A plant that buys a spray unit because it is cheaper, and then doses three times the scavenger to compensate, has bought the wrong machine twice.