What a field test can prove

A field efficiency test is not an acceptance test and should not pretend to be one. It cannot match a laboratory bomb calorimeter and a calibrated rig, and it will not settle a contractual argument about a guarantee. What it can do is establish, within about one percentage point, whether a boiler is near its design efficiency, whether last month’s change helped, and where the losses go. That is enough to justify a repair, a retune or a capital request.

The method is the indirect, or loss, method: measure the losses and subtract them from 100. It is preferred in the field because the losses can be measured with portable instruments, whereas the direct method needs an accurate steam flow and an accurate fuel flow at the same time, and both are hard to get on a working plant. The indirect method also tells you where the loss is, which the direct method does not.

The loss stack, item by item

The field losses are few and they cover most of the gap. The largest is the sensible heat in the dry flue gas: nitrogen, carbon dioxide and excess oxygen leaving above ambient. Next is the heat that leaves as water vapour from combustion and fuel moisture. Then unburnt carbon or CO, small for gas and material for coal or biomass. Finally radiation from the casing at 1-2%, and blowdown at 1-3% of the heat in the water sent to drain.

The dry gas loss can be calculated from the flue gas temperature, the ambient temperature and the oxygen reading, using coefficients that depend on the fuel. For natural gas a workable approximation is: dry gas loss (%) = (flue temperature − ambient temperature) × [0.65/(21 − O2%) + 0.01]. At a 165 °C stack, 25 °C ambient and 4% oxygen, that gives 140 × (0.65/17 + 0.01) = 140 × 0.0482 = 6.7%. Raise the oxygen to 8% and the same stack gives 140 × (0.05 + 0.01) = 8.4%, a loss of 1.7 points from excess air alone.

The coefficients vary with fuel composition, and a test on oil or biomass needs the fuel’s ultimate analysis to do the calculation properly. That is one reason a field test should state its assumptions: the fuel, its calorific value, its sulphur and moisture content, and the reference temperature. Without those, the number is a comparison between two tests, not an efficiency.

The instruments that earn their place

A portable flue gas analyser measuring oxygen, carbon monoxide, flue temperature and ambient temperature is the core instrument. It should be calibrated, and its electrochemical oxygen cell should be checked against air (20.9%) before and after the test. A hand-held thermometer for the feedwater and the ambient, a clamp-on ultrasonic flow meter for the fuel gas or the feedwater, and a stopwatch are the rest of the kit.

Where a gas meter is available, use it rather than the ultrasonic meter; the meter is calibrated and the ultrasonic meter on a small gas line is not. Where steam flow is needed for a direct check, a clamp-on ultrasonic meter on the steam main is acceptable if the pipe is straight and the meter is set for the pipe material and schedule. It is not accurate enough to prove a guarantee but it is accurate enough to catch a 10% error.

One instrument that is often missing is a barometer. The analyser’s oxygen reading is on a dry basis and the calculations assume a reference pressure; at 1,500 m altitude the air density and the excess air calculation shift, and a test that ignores it can be a point out. A phone with a pressure reading is better than nothing.

The protocol: steady state, three loads, one hour

The boiler must be at steady state before the test starts, which means at least 30 minutes at the test load with the feedwater, the steam demand and the burner modulation stable. A boiler that is cycling between high and low fire cannot be tested; the analyser will average two different operating points and produce a number that describes neither.

Test at three loads if the plant can arrange it: high fire, mid load and the minimum stable fire. At each, log the analyser readings every five minutes for an hour, and average them. A single spot reading is not a test; it is a snapshot that can be dominated by a purge cycle or a burner modulation. Record the fuel flow, the steam pressure and the feedwater temperature at the same intervals.

The purges and the cycling are the largest source of error. A boiler that purges every start loses a furnace volume of air each time, and the analyser reads a spike of oxygen that has nothing to do with combustion. Logging over an hour and examining the trend, rather than averaging blindly, lets those events be excluded or weighted.

The arithmetic and its uncertainty

A worked example makes the method concrete. A 10 t/h gas boiler runs at 8.5 t/h with 800 Nm³/h of gas at 36 MJ/Nm³, a 170 °C stack, 20 °C ambient and 3.5% oxygen. Fuel input is 28.8 GJ/h, or 8 MW. Dry gas loss at 150 K and 3.5% oxygen is 150 × (0.65/17.5 + 0.01) = 7.1%. Radiation is 1.2%, blowdown at 4% about 1.2 points, unburnt negligible. The moisture term is where the arithmetic goes wrong: adding the latent heat of the water vapour as a loss, about 10.5 points, gives a total of 20% and an efficiency of 80%, two points below the design.

On an LHV basis the latent heat is already excluded from the fuel’s energy, so adding it again counts it twice. The correct moisture loss is only the sensible heat of the vapour above the reference, 1.2 points at this stack temperature. The total is 7.1 + 1.2 + 1.2 + 1.2 = 10.7%, and the efficiency 89%. That is realistic without a working economiser and a 170 °C stack; the design figure of 93% assumes a 140 °C stack, which the test has shown is not happening.

Measurement Instrument Typical accuracy Effect on result
Oxygen Flue analyser ±0.2% absolute ±0.3 point
Flue temperature Thermocouple ±2 K ±0.1 point
Ambient temperature Thermometer ±1 K Negligible
Fuel flow Gas meter ±1% ±1 point direct
Steam flow Clamp-on ultrasonic ±3-5% ±3-5 points direct
Feedwater temperature Thermocouple ±1 K ±0.2 point

Using the result honestly

The uncertainty of a careful indirect test is about ±1 percentage point, dominated by the fuel analysis and the flue temperature. That means a change of 0.5 points cannot be distinguished from noise, and a claim of a 1-point improvement needs repeated tests on different days. The way to detect a real change is to keep the protocol identical, test before and after under similar ambient conditions, and compare the individual losses rather than the total.

A test that shows 88% where the design says 93% is not necessarily a failed boiler. It may be a fouled economiser, a bypass left open, a burner out of tune, or an ambient temperature 20 K higher than the design. The value of the test is that it separates those causes: high stack temperature points to surface or bypass, high oxygen points to the burner, high CO points to combustion, and a normal stack with low efficiency points to the measurement basis. That diagnosis, not the headline number, is what the test is for.