The same duty, two very different plants

A process needs 2 MW at 280 °C. Steam can deliver it, but saturated steam at 280 °C exists at 6.4 MPa, and a boiler at that pressure is a different class of equipment from the 1.25 MPa units found in most factories. Thermal oil delivers the same temperature at 0.6-0.8 MPa, because the oil does not boil; its pressure is only what the circulating pump needs to overcome the circuit.

That difference in pressure is the start of the comparison, not the end of it. The two systems differ in water treatment, in the energy lost through blowdown and traps, in pump power, in response to load and in what they can do with the heat at the point of use. Each of those has a number attached.

Pressure, temperature and the fluid itself

A liquid-phase thermal oil system is a closed loop: heater, circulating pump, expansion tank, and the user. The oil is chosen for its film temperature limit, typically 300-320 °C for a standard mineral oil and 340-350 °C for a synthetic. Above the film limit the oil cracks, forming carbon and low-boiling fractions that raise viscosity and vapour pressure; the loop then needs venting and eventually a charge replacement.

The pressure in the loop is set by pump head and static height, usually 0.4-0.8 MPa at the heater outlet. Pipes are thin-walled, flanges are standard, and the heater is not a pressure vessel in the same sense as a boiler. That is a real saving in capital cost and in inspection burden.

Steam at 280 °C needs 6.4 MPa, thick drums, forged headers, a demineralisation plant and a licensed operator. Steam at 1.0 MPa, the pressure most factories actually run, is only 184 °C, which is fine for dryers, kettles and sterilisers but cannot reach a 280 °C platen. Many plants that think they need thermal oil actually need steam at 1.6 MPa and a higher-temperature process fluid at the machine.

Energy: latent heat against pump power

Steam carries a large amount of energy per kilogram as latent heat, which is why the mass flow is small. At 1.0 MPa, 2 MW needs 3.6 t/h; at 6.4 MPa, 2 MW needs 4.8 t/h. Thermal oil at a 40 K drop and a specific heat of 2.6 kJ/kg·K needs 69 t/h, roughly twenty times the mass flow of steam at 1.0 MPa.

That large flow is moved by a pump, and pump power is the oil system’s main parasitic load. With a 250 kPa circuit drop and a 65% pump efficiency, 69 t/h of oil at 850 kg/m³ draws about 9 kW, or 15 kW allowing for the heater and control valves. Against 2 MW that is 0.75%, which is small but not zero.

Steam pays in other places. Blowdown at 4% of feedwater discards heat at saturation temperature; on a 1.0 MPa boiler that is about 1% of fuel. Trap losses, flash steam from condensate receivers and condensate that is not returned typically cost another 3-8% of the heat raised, depending on how well the trap population is maintained. Water treatment adds chemicals and regenerate. A well-run steam system with 90% condensate return loses perhaps 5-6% of its fuel to these paths; a neglected one loses 12%.

The oil loop has no blowdown and no flash loss, but it has an annual oil test and a slow degradation cost. A 4 m³ charge at RMB 18,000/m³ is RMB 72,000, and a 5% annual top-up and eventual replacement adds a few per cent of that per year. Against the steam system’s water and trap losses, the oil loop usually wins on energy by 4-7% at this temperature, which is worth having but is rarely the deciding factor.

Item Thermal oil at 280 °C Steam at 1.0 MPa
Operating pressure 0.6-0.8 MPa 1.0 MPa
Temperature available Up to 300-320 °C 184 °C saturated
Flow for 2 MW About 69 t/h About 3.6 t/h
Pump power 12-18 kW 4-6 kW
Blowdown loss None About 1% of fuel
Trap and flash loss None 3-8% of heat raised
Water treatment None Softening or demineralisation
Direct injection into product Not possible Standard practice
Fire risk on leak Oil above its flash point Steam, not combustible

Where steam is the only sensible answer

Steam does things oil cannot. It can be injected directly into a product for cooking, sterilisation or humidification, which is why food, pharmaceutical and hospital processes use it. It drives ejectors and vacuum systems, it atomises fuel in burners, it provides the latent heat that makes a jacketed vessel behave predictably, and it is the standard utility in laundries and autoclaves.

Steam also tolerates a distributed network better. A 200 m steam main with proper trapping and drainage is routine; a 200 m hot oil main needs careful expansion design, a large expansion tank, and a leak that drips hot oil at 280 °C is a fire risk wherever it lands. Plants that need heat in several buildings usually choose steam for that reason alone.

The steam system’s weakness is its auxiliary plant. A 6.4 MPa boiler needs demineralised water, a deaerator, a blowdown system and trained operators. A plant that installs a high-pressure steam boiler for one 280 °C press has bought a utility department to run one machine.

Selection rules

Choose thermal oil for a closed, high-temperature process loop at 250-320 °C where the heat is used indirectly through a heat exchanger, jacket or platen, and where the plant has no other steam demand. Typical users are plywood and board presses, asphalt and bitumen tanks, chemical reactors, textile stenters and calenders, and food fryers. In these duties the oil system is smaller, cheaper to install, needs no water treatment and runs at low pressure.

Choose steam where the process needs latent heat, direct contact, sterilisation, or a plant-wide utility at 0.4-1.6 MPa, and where the temperature requirement is below about 200 °C. That covers most food, beverage, pharmaceutical, textile and hospital loads.

Where both are needed, run steam as the plant utility and use a packaged thermal oil heater for the one or two high-temperature users. That avoids a 6.4 MPa boiler house and keeps the oil loop small enough to be maintained by the process team rather than a utility department.

The calculation to settle it is straightforward: add the oil system’s pump power, oil replacement and heater efficiency, and compare with the steam system’s blowdown, trap losses, water treatment and the capital cost of the higher pressure. If the site needs direct steam anywhere, that usually settles the argument before the energy comparison begins.