Three numbers, one compromise

A gas burner has three measured outputs that matter: oxygen in the flue gas, carbon monoxide, and oxides of nitrogen. They are not independent. Adding air reduces CO and raises the mass of gas going up the stack; removing air improves efficiency until CO rises sharply and unburnt fuel leaves the boiler. Changing the air also changes flame temperature, which moves NOx. Tuning is the business of finding the point where those three are acceptable at every load, and most burners in the field are set somewhere other than that point.

The instrument is a portable flue gas analyser, and the reading that gets written on the commissioning sheet is usually oxygen. That is reasonable, because oxygen is the one variable the burner can control directly and the one that maps most cleanly onto excess air. What matters is that the number is recorded at several loads and that the person doing the recording understands what each point costs.

Excess air and the heat that leaves with it

Complete combustion of natural gas needs 9.52 Nm³ of air per normal cubic metre, and a burner runs above that figure because perfect mixing is impossible. At 3% oxygen dry in the flue gas, excess air is about 15%; at 6%, about 36%; at 9%, about 68%. The excess air does no chemical work. It enters cold, leaves hot, and every kilogram of it carries sensible heat out of the boiler.

The loss is easy to estimate. Dry flue gas loss is roughly proportional to the gas mass flow and the temperature difference between the stack and the ambient air. As a working rule for natural gas at a stack temperature of 180 °C, each 1% of oxygen above the optimum costs about 0.5% of fuel, and the difference between a well-tuned burner at 3% and a neglected one at 9% is around 3% of the fuel bill. On a 6 t/h boiler running 6,000 hours a year it is the largest untended item in the budget.

Stack temperature and excess air multiply. A burner at 9% oxygen and a stack at 250 °C, because the economiser is bypassed or fouled, can lose 12-14% of the fuel input up the chimney. The same boiler tuned to 3% oxygen with a clean economiser and a 150 °C stack loses 5-6%. The gap is the difference between an efficiency of 86% and one of 94%, and neither figure requires new equipment.

CO: the limit on how little air you can use

Carbon monoxide is the signature of incomplete combustion. It appears when the flame is cooled below the temperature at which CO oxidises to CO2, when there is not enough oxygen locally, or when the fuel and air are poorly mixed. In a well-set gas flame, CO is below 20 ppm and often below 5 ppm. Above 100 ppm there is a real loss of chemical energy, and above 400 ppm the burner is producing soot and unburnt hydrocarbons as well, which foul the convection bank and the economiser.

The temptation, when chasing efficiency, is to keep cutting air until CO appears and then back off slightly. That is the right method but the wrong margin. A burner set with 10 ppm of CO at full load will produce several hundred ppm at 30% load, because the mixing quality degrades as the fuel pressure and the air velocity fall. The tuning must be done at each load point, and the CO limit should be set for the worst point, not the best one.

There is also a safety dimension. CO in the flue gas is a warning of a flame that is unstable, and a flame that is unstable at low load can lift off or extinguish. The flame detection system is the last line of defence, not the tuning method. A burner that needs to run at 1.5% oxygen to hold efficiency is a burner with a mixing problem, and the answer is a new burner head or a different diffuser, not a lower air setting.

NOx and the trade nobody escapes

Thermal NOx forms in the flame at temperatures above about 1,500 °C, and its rate rises exponentially with temperature. Lowering excess air raises the flame temperature and increases NOx; raising excess air cools the flame and lowers NOx but costs efficiency. That is the fundamental trade, and it is why low-NOx burners use flue gas recirculation, staged air and a larger furnace instead of simply running lean.

A standard gas burner might produce 120-150 mg/Nm³ of NOx at 3% oxygen; a low-NOx version with internal recirculation reaches 60-80, and a unit with external recirculation and staged combustion reaches 30. Each step costs fan power, furnace volume or both. If the limit is 30 mg/Nm³, the burner must be designed for it; no amount of tuning will take a standard head to that figure without unacceptable CO.

Tuning across the load range

The procedure is mechanical and repetitive. Run the boiler to normal operating temperature with the process load stable. Start at high fire, set the air damper to give the target oxygen with CO below the limit, then repeat at 75%, 50% and the minimum stable fire. Record oxygen, CO, NOx, stack temperature and ambient temperature at each point. Then set the linkage or the electronic cam so that the oxygen curve is flat or rises slightly as load falls, because mixing deteriorates at low fire and a little more air is cheaper than a lot of CO.

The final step is to lock the settings and record them. A burner that is tuned and then left unlocked will be adjusted by the next shift to stop a rumble, and the efficiency gain disappears. Where the boiler has oxygen trim, the trim should be enabled only after the base curve is correct, with a dead band wide enough that it does not hunt. Trim on a badly set curve amplifies the error instead of correcting it.

Reading the flame and the numbers

The table gives typical figures for a packaged gas boiler at 180 °C stack temperature. The efficiency column is the combustion efficiency from flue loss alone; radiation and blowdown are separate.

Oxygen, dry Excess air Flue loss at 180 °C Typical CO Comment
2% 10% 4.6% 50-200 ppm Lean limit, unstable at low load
3% 15% 5.2% 10-30 ppm Normal target for gas
5% 29% 6.4% 5-15 ppm Safe but wasteful
7% 48% 7.7% 5-10 ppm Common on untuned plant
9% 68% 9.1% 5-10 ppm Costs about 3% of fuel

A flame that is yellow-tipped, long and smoky is short of air; a flame that is short, noisy and lifting is in excess. On a packaged WNS or SZS boiler the flame should be visible through the sight glass as a stable, bright core with no impingement on the tube sheet. The analyser confirms what the eye suspects, and the two together are worth more than either alone.

The economics of tuning are unusual because the cost is almost entirely labour. A half-day with an analyser, a competent technician and a written record will recover two to five points of efficiency on a boiler that has not been touched for years, and the improvement persists until someone adjusts the linkage. Making the tuned figures part of the shift log, and re-checking them after every burner service, is what keeps the gain. A burner is not tuned once; it is tuned and then defended.