SZS Water-Tube Gas/Oil Steam Boiler, 6-100 t/h
Membrane-wall water-tube steam boiler with staged combustion and FGR, 6-100 t/h at up to 2.5 MPa and 98% efficiency with heat reco...
View detailsA 6 t/h gas steam boiler at 1.25 MPa supplies dyeing and finishing in Shymkent, with a low-NOx burner, economizer and a feedwater system sized for hard local water.

The plant processes cotton and finishes fabric in Shymkent, where the mains water is hard enough that scale, not fuel, is the main operating risk. Steam demand runs at 4-5 t/h for two shifts, with a 5.5 t/h peak when the dye house and the stenters overlap. The boiler is a 6 t/h WNS fire-tube unit at 1.25 MPa.
Feedwater is the part of this installation the plant notices most. A softener sized for 8 m3/h reduces hardness to under 0.03 mmol/L, and a thermal deaerator at 105 °C removes oxygen before the water reaches the boiler. Without the softener, a fire-tube boiler at this hardness would scale the furnace tube within a season.
The WNS is a three-pass wet-back unit with a corrugated furnace. At 6 t/h and 1.25 MPa it absorbs about 4.2 MW; on natural gas at 35 MJ/Nm3 and 94% efficiency the full-load gas rate is roughly 460 Nm3/h. The burner is a low-NOx type with flue-gas recirculation, and the economizer takes the stack down to about 140 °C.
| Item | Value |
|---|---|
| Rated evaporation | 6 t/h |
| Pressure / temperature | 1.25 MPa / 194 °C |
| Absorbed duty | about 4.2 MW |
| Full-load gas rate | about 460 Nm3/h |
| Feedwater hardness | below 0.03 mmol/L |
| Blowdown | automatic, on conductivity |
Shymkent is milder than northern Kazakhstan but still sees -10 to -15 °C, and the boiler house was originally unheated. The plant added a small space-heating circuit off the boiler and insulated the feedwater tank and the deaerator, which cut standby losses and stopped the economizer from freezing during weekend shutdowns. The gas train is indoors and trace-heated where it runs outside.
The burner was set up on the local gas analysis, which is leaner than the methane figure used for the initial selection. The commissioning engineer re-set the combustion curve on site with a flue-gas analyser, and the plant now checks O2 and CO monthly rather than annually.
The boiler has run two seasons without a tube failure. Steam pressure holds within 0.05 MPa at the dye-house header, and the plant’s specific gas consumption is about 76 Nm3 per tonne of steam, against 82 before the economizer was commissioned. The softener resin is the maintenance item: it is regenerated daily and replaced every three years.
External links open the publisher’s website and are provided for background reading.
Scale on the furnace tube raises metal temperature and can cause a tube failure. At 1.25 MPa the limit is usually 0.03 mmol/L hardness or lower.
About 76 Nm3 per tonne at 94% efficiency and 35 MJ/Nm3 gas, including the economizer.
Yes, with a different gas train and burner orifice. The combustion curve has to be re-set because the Wobbe index differs.