Choosing between natural gas and LPG for an industrial boiler is rarely just a question of which fuel is cheaper per unit. The decision hinges on calorific value, how the fuel is stored and vaporised, what burner modifications are needed, and ultimately the delivered cost per tonne of steam. This article breaks down those factors with real engineering values and assumptions, so you can evaluate the trade-offs for your site.

Calorific value and energy density

Natural gas (NG) and LPG differ significantly in energy content per unit volume and per unit mass. The table below summarises typical values, using gross calorific value (GCV) on a volumetric basis for gases and a mass basis for LPG. Assumptions: NG composition ~95% methane, LPG commercial propane (C3H8) with minor butane. Values are indicative and vary by source.

Property Natural Gas LPG (Propane)
GCV (MJ/Nm³) ~38–39 ~93–95 (vapour)
GCV (MJ/kg) ~52–54 ~50
Density (kg/Nm³) ~0.72–0.78 ~2.0 (vapour)
Wobbe index (MJ/Nm³) ~48–52 ~72–76
Stoichiometric air/fuel ratio (vol) ~9.5–10 ~23.8

Per kilogram, the two fuels are similar in energy content, but per normal cubic metre LPG carries about 2.4 times the energy of NG. This affects pipe sizing and burner orifice design. The higher Wobbe index of LPG means burner injectors must be sized differently to achieve the same heat input.

Storage and site requirements

Natural gas is typically supplied via pipeline, requiring no on-site storage. LPG, however, must be stored as a liquid under pressure (approx. 7–8 bar at ambient temperature) in tanks or cylinders. A common bulk tank size for industrial use is 10–20 m³, but the required capacity depends on consumption and delivery frequency. For a boiler consuming 1 tonne/hour of steam, typical fuel input is around 2.8–3.0 MW. Using LPG at 50 MJ/kg, that equates to roughly 200–215 kg/h of LPG. A 10 m³ tank holds about 4.2 tonnes of propane (at ~420 kg/m³ filling density), giving roughly 20 hours of continuous operation at that rate. Sites without pipeline access must consider tank footprint, safety distances, and delivery logistics.

Vaporisation and supply pressure

LPG must be vaporised before combustion. For small-to-medium boilers, natural vaporisation from the tank may suffice, but at higher draw-off rates an external vaporiser is needed. The vaporisation capacity depends on tank surface area, ambient temperature, and fuel composition. As a rule of thumb, a 10 m³ tank can naturally vaporise about 30–50 kg/h of propane at 10°C ambient; beyond that, a forced vaporiser is required. The vaporiser must be sized to match the boiler’s maximum fuel demand plus a margin. Natural gas, by contrast, is already gaseous and only needs pressure reduction from the distribution main (typically 2–4 bar) to the burner manifold (e.g., 20–50 mbar for many industrial burners).

Burner change and combustion considerations

Switching between NG and LPG requires more than a simple adjustment. Burners are fuel-specific: the gas train, injectors, and control valves are sized for the fuel’s calorific value, density, and Wobbe index. A burner configured for NG will not operate safely on LPG without modification. Typically, the burner manufacturer supplies a conversion kit that includes new gas nozzles, a different gas valve train, and revised combustion head settings. The boiler itself may remain unchanged, but the flue and ventilation may need review due to different stoichiometric air requirements. LPG requires about 23.8 volumes of air per volume of gas, compared to about 9.5–10 for NG, so air supply and flue sizing must be checked. Also, LPG is heavier than air and can accumulate in low areas, so leak detection and ventilation design must account for this.

Delivered cost per tonne of steam

The delivered cost per tonne of steam is the most practical metric for comparing fuels. It depends on fuel price per unit, boiler efficiency, and the energy required to produce one tonne of steam. Consider a boiler producing saturated steam at 10 bar g from feedwater at 100°C. The enthalpy of steam at 10 bar g is approximately 2780 kJ/kg, and feedwater enthalpy at 100°C is about 419 kJ/kg, so the useful heat required is roughly 2361 kJ/kg (or 2361 MJ/tonne). With a boiler efficiency of 85% (GCV basis), the fuel energy input per tonne of steam is about 2361 / 0.85 ≈ 2778 MJ/tonne.

For natural gas with GCV of 38.5 MJ/Nm³, this equates to about 72 Nm³ per tonne of steam. For LPG with GCV of 50 MJ/kg, it equates to about 55.6 kg per tonne of steam. To compare costs, you need the delivered price per Nm³ of NG and per kg of LPG. Because prices vary widely by region and contract, we do not quote figures here. Instead, calculate: cost per tonne steam = (fuel input per tonne) × (fuel price per unit). For example, if NG costs X per Nm³, the fuel cost per tonne of steam is 72X. If LPG costs Y per kg, it is 55.6Y. The break-even price ratio is Y/X = 72/55.6 ≈ 1.29. In other words, LPG can be competitive if its price per kg is less than about 1.29 times the NG price per Nm³ (on an energy-equivalent basis). However, this ignores differences in efficiency, maintenance, and storage costs, which can tip the balance.

Checklist: evaluating NG vs LPG for your site

  • Confirm available fuel supply: pipeline NG or LPG delivery infrastructure.
  • Calculate peak and average steam demand to size fuel storage and vaporisation.
  • Check burner compatibility and budget for a conversion kit if switching.
  • Review site safety: LPG requires hazardous area classification and ventilation.
  • Compare delivered fuel prices on an energy basis (per MJ) and include storage/vaporiser OPEX.
  • Assess flue and air supply adequacy for the chosen fuel.
  • Consider future fuel flexibility: dual-fuel burners are available but add cost.

What to send us for a proposal

To prepare a tailored proposal for an NG or LPG boiler, please provide: required steam capacity (kg/h or tonnes/h), operating pressure and temperature, expected load profile, available fuel type and supply details (e.g., NG pressure or LPG tank size), site constraints (space, safety distances), and any preference for dual-fuel capability. Also include your current boiler efficiency and fuel consumption if replacing an existing unit. With this information, we can recommend a boiler from our product range and provide a detailed cost analysis. For further guidance on sizing and cost factors, refer to our capacity and cost guide.