35 t/h
35 t/h Water-Tube Gas/Oil Steam Boiler SZS35-1.6-Q
The SZS35-1.6-Q is a 35 t/h D-type double-drum water-tube boiler delivering 1.6 MPa steam at 204°C. It fires natural gas, LPG, lig...
View detailsThe WNS8-1.25-Q is an 8 t/h packaged three-pass wet-back fire-tube steam boiler rated at 1.25 MPa and 194 °C, firing natural gas, LPG, light diesel or heavy fuel oil at 95% efficiency (LHV basis).

The WNS8-1.25-Q is an 8 t/h unit in the WNS gas/oil steam boiler series. It is a three-pass wet-back fire-tube boiler, factory-packaged and fitted with a low-NOx burner. Rated steam pressure is 1.25 MPa at a steam temperature of 194 °C. The boiler fires natural gas, LPG, light diesel or heavy fuel oil, and is rated at 95% efficiency on an LHV basis.
At 8 t/h, this model sits in the mid-range of packaged fire-tube practice. It suits plants whose steam demand runs continuously in the region of several tonnes per hour with moderate peaks, such as food and beverage processing, textile finishing, paper converting, chemical batch processing, and district or campus steam networks. It is also a common choice where a single boiler must carry the base load with one standby unit, rather than a battery of smaller boilers.
The published fuel consumption is 594 Nm³/h at rated output on natural gas at 95% efficiency. The figure follows from the rated output and the fuel’s lower heating value: the boiler must deliver 8 t/h of steam at the stated pressure and temperature, and the fuel volume is the heat input required to do so divided by the LHV of natural gas, adjusted for the 95% efficiency. Because the rating is on an LHV basis, the figure is directly comparable with gas supplier data stated on the same basis. Consumption with LPG, light diesel or heavy fuel oil differs with the fuel’s heating value and must be calculated for the specific fuel.
An 8 t/h fire-tube boiler with a modulating low-NOx burner typically holds efficiency well across the middle of its range and loses some efficiency at the low end, where fixed losses such as radiation and stack loss become a larger share of input. At this capacity the water volume and thermal mass are substantial, so the unit tolerates short demand swings without rapid cycling. For sustained loads well below the mid-range, a smaller unit or staged operation is usually more economical than running this boiler at minimum fire.
The WNS8-1.25-Q is a packaged, shop-assembled unit: the pressure vessel, burner and controls ship as one assembly, which simplifies site work compared with field-erected boilers. Planning should account for a boiler room with adequate floor area for the packaged unit and its burner, clearance for tube access and inspection at the ends, space for the flue and stack connection, and room for fuel train and feedwater equipment. Foundations must carry the operating weight of the water-filled boiler. Confirm the actual arrangement against the general arrangement drawing for the project.
Fire-tube boilers of this size depend on consistent feedwater treatment. Scale and deposits on the furnace and tube surfaces raise metal temperatures and reduce efficiency; oxygen and low pH promote corrosion. A treatment programme matched to the local feedwater, with routine blowdown and monitoring of boiler water chemistry, is part of normal operation. Water treatment requirements should be set by the water treatment supplier against the feedwater analysis.
The packaged unit is supplied with a burner management and boiler control system. Modulation of the low-NOx burner matches firing rate to steam demand; safety interlocks supervise flame, pressure and water level. Control scope and interface details should be confirmed against the project specification.
Choosing 8 t/h rather than the next size down gives margin for peaks and for future load growth without running a smaller boiler flat out; choosing it rather than the next size up avoids paying for capacity that would sit idle and cycle at low fire. Where the load profile is steady and well known, the neighbouring sizes in the series may fit better; the 8 t/h model is the practical middle when demand is moderate but not fixed.
| Parameter | Value |
|---|---|
| Model | WNS8-1.25-Q |
| Capacity | 8 t/h |
| Rated pressure | 1.25 MPa |
| Steam temperature | 194 °C |
| Feedwater temperature | Not specified in brief |
| Fuel | Natural gas, LPG, light diesel, heavy fuel oil |
| Fuel consumption at rated output | 594 Nm³/h (natural gas, 95% efficiency) |
| Efficiency | 95% (LHV basis) |
| Burner/control | Low-NOx burner; packaged three-pass wet-back fire-tube |
| Application | Process and heating steam, mid-range continuous duty |
It is rated at 8 t/h of steam at 1.25 MPa and 194 °C. The burner modulates to match demand, and the practical continuous load depends on the plant's load profile and water treatment.
594 Nm³/h of natural gas at rated output, based on 95% efficiency on an LHV basis. Consumption with LPG, light diesel or heavy fuel oil differs with the fuel's heating value.
Yes. The packaged fire-tube design with a modulating low-NOx burner handles moderate swings, though sustained operation far below mid-range is less efficient than running a smaller unit or staging boilers.
| Model | WNS8-1.25-Q |
|---|---|
| Capacity | 8 t/h |
| Rated pressure | 1.25 MPa |
| Steam temperature | 194 °C |
| Feedwater temperature | Not specified in brief |
| Fuel | Natural gas, LPG, light diesel, heavy fuel oil |
| Fuel consumption at rated output | 594 Nm³/h (natural gas, 95% efficiency) |
| Efficiency | 95% (LHV basis) |
| Burner/control | Low-NOx burner; packaged three-pass wet-back fire-tube |
| Application | Process and heating steam, mid-range continuous duty |
External links open the publisher’s website and are provided for background reading.
Include the capacity (t/h or MW), fuel, working pressure and site country so the proposal matches your permit limits.
We appoint one or two partners per country to quote, deliver and service our boilers locally. Territory protection, factory pricing and commissioning support are part of the agreement.