Direct and indirect: what the separation costs

A hot air furnace for drying can be built in two ways. Direct firing puts the combustion products into the drying air: the burner or the coal bed discharges into a mixing chamber, the gas is diluted to the required temperature, and the whole mixture goes to the dryer. Indirect firing puts a heat exchanger between them: the combustion gas passes through tubes or a shell, the clean air passes over the outside, and only heat crosses the boundary.

Direct firing is more efficient, because there is no heat exchanger to lose temperature across and no stack to carry heat away. A direct coal furnace reaches 92-95% of the fuel’s heat into the drying air. An indirect one reaches 70-80%, because the flue gas leaves the exchanger at 180-250 °C and the radiation and convection losses from a hot casing are real. That 15-20 point difference is the price of separation, and it is worth paying whenever the product cannot tolerate combustion products.

For coal the answer is almost always indirect. Coal flue gas carries fly ash, sulphur dioxide and, depending on the coal, fluoride and chloride. A direct-fired coal dryer deposits ash on the product and gives it a smell that no amount of subsequent processing removes. Indirect firing is not a refinement; it is the only way coal can be used for food, grain, tea, timber, ceramics and most chemical drying.

Temperature limits

The limiting component is the heat exchanger tube or shell. Carbon steel at 450 °C is the practical ceiling for continuous service, and the metal runs hotter than the air it heats, so the clean air outlet is normally limited to 300-350 °C. Above that the tube material moves to a heat-resistant stainless and the cost rises steeply. This is why indirect coal hot air furnaces are offered with outlet temperatures of 80-300 °C and why a requirement for 400 °C air changes the technology rather than the model.

The flue gas side has its own limit. Coal combustion produces a flue gas at 900-1,100 °C at the chamber exit, and the first tube pass must be protected by refractory or by a dilution of recirculated gas. Air velocity inside the tubes is held at 8-12 m/s: too low and the tube wall runs hot and fouls, too high and the fan power outweighs the gain.

The heat balance of a drying duty

Drying loads are calculated on water evaporated, not on product throughput. Lifting one kilogram of water out of a material and into the exhaust air takes roughly 2,600 kJ of latent heat plus the sensible heat of the material, so 3,000 kJ per kilogram is a working figure for a well-designed dryer.

Take a dryer that must evaporate 1,000 kg of water an hour, which is a medium-sized grain, timber or ceramic installation. That is 3,000 MJ/h, or 833 kW, at the dryer. An indirect coal furnace at 75% efficiency must supply 1,111 kW of fuel power, which at 20 MJ/kg is 200 kg/h of coal. Per kilogram of water evaporated, the coal consumption is about 0.2 kg. A gas-fired indirect furnace at 92% needs 905 kW, or 91 Nm³/h.

Those figures scale linearly and they are the ones to argue about at the quotation stage. A furnace quoted at 85% efficiency on coal is claiming something the heat balance does not support unless it has an air preheater or a condensing tail, and neither is common on a coal unit. Ask for the flue gas temperature at the outlet and the casing surface temperature, and the efficiency claim becomes checkable.

Annual fuel follows: 200 kg/h over 4,000 hours is 800 tonnes of coal a year, with 15-25% ash, which is 120-200 tonnes of ash to handle, store and dispose of. That number, more than the fuel bill, is what drives most sites to look at alternatives.

Dust, leakage and carbon monoxide

An indirect furnace has two gas streams that must never mix, and the failure mode is a tube or a weld that cracks. When that happens, flue gas at 2-8 g/Nm³ of dust enters the drying air and the product is contaminated — usually discovered when the batch is already spoiled.

Three defences. Run the clean air side at 200-500 Pa above the flue side, so any leak goes the safe way, from clean to dirty. Fit a carbon monoxide detector in the clean air outlet: a rise in CO means combustion gas is crossing, and it responds faster than a visual check. And provide a manual isolation damper and a bypass so the furnace can be taken out of the drying circuit without stopping the dryer, which lets the tubes be inspected on a schedule rather than after a failure.

The flue side needs its own dust removal. A coal furnace on a chain grate produces 2-8 g/Nm³, and a cyclone is adequate for the furnace itself even where the main boiler has a bag filter, because the dust never reaches the product. What the cyclone does not do is protect the site’s stack from a visible plume, so where the furnace shares a stack with a boiler under a 20 mg/m³ limit, the bag filter has to cover both.

When gas or biomass wins

Coal hot air furnaces survive where coal is cheap, the emission limit is loose, and labour is available to stoke, de-ash and clean tubes. Each of those conditions is disappearing. A 1 MW furnace burns 200 kg/h, which is a tonne and a half a day, delivered, stored, moved and de-ashed by somebody; the ash is 30-40 kg/h and has to go somewhere.

Gas is the straightforward replacement where a main is available: no ash, no dust, 92% efficiency, modulation down to 20%, and a burner that needs no operator. The capital cost is the burner and the gas connection, and the furnace itself is smaller because there is no grate or ash pit.

Biomass sits between them. A biomass hot air furnace with an indirect exchanger reaches 72-78% and burns 240-280 kg/h of wood chip at 15 MJ/kg for the same duty. It is carbon-neutral in accounting terms and usually compliant on sulphur, but it brings its own ash, its own clinker risk on the grate, and a fuel store that has to be kept dry. For a site with a sawmill or an agricultural residue stream, that is a good trade; for a site buying biomass at market price, the case is weaker than the sales literature suggests.

Comparison for a dryer evaporating 1,000 kg of water per hour
Item Coal, indirect Biomass, indirect Gas, indirect
Fuel for 833 kW drying 200 kg/h 250 kg/h 91 Nm³/h
Furnace efficiency 70-80% 72-78% 90-93%
Ash 30-50 kg/h 5-12 kg/h None
Air outlet limit 300-350 °C 300-350 °C 350-400 °C
Turn-down 2:1 2.5:1 5:1
Operator attention 2-3 h per shift 1-2 h per shift Daily check

What the enquiry needs

Water evaporated per hour, the drying air inlet and outlet temperatures, the maximum permissible contamination of the product, the fuel available and its analysis, the emission limit that applies, and the hours per year. Those six answers decide whether the furnace is direct or indirect, coal or gas or biomass, and what the real annual cost is once ash and labour are counted.