Two boilers, four ways to run them

A plant with two or three boilers has a control problem that a single boiler does not. The units can run in parallel at equal load, in series as lead and lag, one at a time with rotation, or in a sequence based on efficiency rather than pressure. Each choice produces a different fuel consumption from the same equipment, and the difference is large enough to pay for the control system several times over.

The reason is the part-load curve. A packaged boiler is most efficient at 70-100% of rating and loses 3-6 points at 30-40%, partly to radiation and fan power, partly to cycling. Two WNS units at 40% are worse than one at 80%, because both pay the fixed losses. Sequencing exists to keep as few units as possible near their efficient band.

Lead-lag and the case for rotation

The simplest scheme is lead-lag: one boiler modulates to hold the header pressure and the second starts when the lead reaches its maximum. The lead then stays at full output and the lag modulates, or both are brought to a common load by a proportional signal. The scheme is easy to understand and easy to commission, and it is what most small plants have.

Its weakness is wear. The lead boiler runs all the time, accumulates hours and starts, and the lag sits idle and corrodes. A boiler that never runs is not a spare; it is a liability with a wet shell and a stale burner. Rotation, on a weekly or monthly basis, equalises the hours and keeps both units exercised. The changeover should be automatic, at low load, with a defined sequence: start the incoming boiler, bring it to pressure, transfer the load, shut down the outgoing unit.

The rotation period is a compromise. Too frequent and the changeover losses (purge, warm-up, thermal cycling) outweigh the benefit; too rare and the standby unit is cold and unreliable. A weekly rotation on a two-boiler plant is common, with the change made at a quiet period and the standby unit run at low fire for an hour before it takes load.

Staging on pressure, and why it hunts

Staging by header pressure uses a pressure band per boiler: the lead runs between 0.8 and 1.0 MPa, the lag starts at 0.95 and stops at 1.05, and a third unit has a wider band. The scheme is robust and needs no communication between boilers, which is why it survives in old plants. It also hunts: a lag boiler that starts at 0.95 and stops at 1.05 will cycle if the load sits near the threshold, and each cycle carries a purge loss and a thermal shock.

The cure is deadband and delay. A staging threshold should be crossed for several minutes before the boiler starts, and the stop threshold should be well below the start threshold, not a few kilopascals above it. A lag boiler should also be brought on at minimum fire and ramped, not started at full output. These are simple settings, and they are the ones most often left at their default settings.

Pressure staging also ignores efficiency. The lead boiler may be the least efficient unit in the house, simply because it was installed first. A sequencing controller that knows each boiler’s efficiency curve can choose the lead by load rather than by age, and can decide whether to run one unit at 90% or two at 45% on the basis of measured fuel input, not a rule of thumb.

Load allocation: proportional or best-point

Once two boilers are running, the controller must divide the load between them. Proportional allocation gives each boiler the same percentage of its rating, which is simple and keeps them at the same point on their curves. Best-point allocation gives more load to the more efficient unit until it reaches its optimum, then brings the other up. The second saves fuel but needs reliable efficiency data and a controller that can act on it.

For most industrial plants, proportional allocation with a bias toward the newer or more efficient unit is the practical answer. The gain from full optimisation is small compared with the gain from simply not running two boilers at 35% each. The sequencing decision, not the allocation algorithm, is where the money is.

Minimum fire is the constraint that decides when a boiler should stop rather than modulate lower. A gas burner typically has a turndown of 5:1, so a 4 t/h boiler cannot run below 0.8 t/h without cycling. If the load is 1.2 t/h, one boiler at 30% is cycling and two at 15% cannot run at all; the correct answer may be a smaller boiler, a steam accumulator, or accepting the cycling with a larger water volume. The control system can only work within the equipment’s limits.

Hot water, steam and the condensing case

Hot water plants add a variable that steam plants do not have: return temperature. A condensing boiler only condenses when the return is below about 50 °C, and a sequencing strategy that runs all boilers in parallel at low load raises the return temperature and kills the condensing gain. The better strategy is to run one boiler at high output with a low return, and to bring the second on only when the first cannot hold the flow temperature. That is the opposite of the equal-load instinct, and it is worth 3-5 points on a condensing installation.

Steam plants have the opposite problem: the header pressure is the control variable and the boilers are effectively in parallel, so the load division is set by their pressure settings unless a common controller overrides them. A steam plant with two boilers at different pressure bands will always run the lower band first, regardless of efficiency, unless the controller is given authority over both.

Strategy Basis Best for Weakness
Lead-lag, fixed lead Header pressure Two boilers, steady load Unequal hours, standby corrosion
Lead-lag with rotation Pressure plus schedule Two or three boilers Changeover losses
Pressure staging Pressure band per unit Old plants, no comms Hunting near thresholds
Efficiency-based Measured fuel per tonne Mixed boiler ages Needs reliable data
Condensing priority Return temperature Hot water, condensing Needs low return

What to specify in the control system

The specification should name the sequence, the thresholds, the delays, the rotation period and the failure mode. It should require a trend of each boiler’s load, starts, hours and fuel input, because without that record no one can tell whether the sequence is working. It should define what happens when a boiler trips: the next unit starts automatically, the header pressure is protected, and the plant alarm is raised.

The controller should also be able to run in manual, boiler by boiler, for maintenance and testing. A sequence that cannot be overridden is a sequence that will be bypassed by a jumper when it misbehaves, and then the plant is back to hand control with no record of why. The best systems are simple enough to explain on one page and instrumented enough to prove they are working.

The savings from good sequencing are not dramatic per hour, but they run for the life of the plant. Keeping one boiler at 80% instead of two at 40% is worth 3-5 points of efficiency, and rotating the lead is worth the avoided cost of a corroded standby shell. Both are control decisions, and both are cheaper than a new boiler.