Two duties that are not the same

A boiler chimney is asked to do two jobs. It must generate enough draught to pull combustion products out of the boiler at every firing rate, and it must discharge those products high enough and fast enough that they do not come back into a window, an air intake or a neighbouring roof. On a modern packaged gas boiler the first duty has almost disappeared, because the burner fan pressurises the furnace and the chimney is only a duct. The second duty has become more important, because low NOx combustion produces a plume that is wetter and often cooler than the one the chimney was built for.

Getting this wrong is expensive both ways. A stack that is too short puts NOx and odour at roof level and fails the planning condition; one that is too tall is a steel structure with foundations and guy wires that can cost more than the boiler. The answer is the shortest stack that satisfies dispersion at the worst case.

Natural draught, for the cases that still use it

Where the boiler has no forced draught fan, or where a biomass or coal unit relies on an induced draught fan downstream, the chimney’s buoyancy matters. The available draught is the difference between the weight of the hot gas column inside the stack and the same column of cold air outside, or (air density minus gas density) × 9.81 × stack height.

With ambient air at 1.2 kg/m³ and flue gas at 160 °C at about 0.82 kg/m³, the difference is 0.38 kg/m³, and a 20 m stack gives 0.38 × 9.81 × 20 = 75 Pa. Raise the gas temperature to 250 °C and the figure rises to about 105 Pa; cool it to 80 °C and it falls to 40 Pa. That is the whole reason condensing boilers cannot rely on natural draught: the gas leaving a condensing economiser at 50-60 °C has almost no buoyancy left.

Those numbers are small against the resistance of a boiler, an economiser and a duct run, which is why anything above a few hundred kilowatts has a fan. The chimney then works under pressure and its height is set by dispersion, not draught. Check that the fan can overcome the stack’s resistance at design flow.

Height: what actually governs it

Dispersion is governed by the building the stack serves and by its neighbours. A plume leaves the stack and is bent over by the wind; if the stack is shorter than the turbulent wake of the roof, the plume is drawn down into it and concentrations at roof level rise sharply. The classical rule is that the stack should discharge at least 1.5 times the height of the building it serves, and preferably 2.5 times where there are taller buildings nearby. For a 10 m boiler house that means a 15-25 m stack, which is often more than the plant expected.

Exit velocity matters as much as height. Below about 5 m/s the plume has little upward momentum and can be caught by the stack’s own cap or by downdraught; above about 20 m/s the pressure drop and noise become significant. The usual design band is 10-15 m/s at full load, with a turndown check at minimum firing rate. A stack sized for 12 m/s will run at 4-6 m/s at 30% load, which is acceptable; one sized for 20 m/s wastes fan power at the top end.

Local rules add their own numbers: often 3 m above the roof ridge within a certain distance, taller than any window within 15-20 m, and sometimes a minimum discharge height for NOx. Those rules are a floor, not a design method. A stack that satisfies them can still put a plume into the recirculation zone of a taller building across the road.

Diameter, velocity and the cost of being too big

Flue gas volume follows the fuel input. Natural gas produces about 11-12 Nm³ of wet flue gas per Nm³ burned at 10-15% excess air, or roughly 1.3 Nm³ per kWh of fuel input. A 4 t/h boiler at 3.2 MW input therefore makes about 4,200 Nm³/h at standard conditions, which at 160 °C is 6,600 m³/h actual. At 12 m/s that needs 0.153 m², or a 440 mm bore; the nearest standard size is 450 or 500 mm.

Oversizing the diameter is a common mistake made in the name of future capacity. A stack that is too large runs at low velocity, cools the gas against its own walls and drops below the dew point before the top, which means rain inside, corrosion at the base and a plume at the cap. If future capacity is real, fit the right diameter now and replace the top section later.

Temperature, moisture and the visible plume

Gas flue gas contains 15-18% water vapour and has a dew point of 55-60 °C. A non-condensing boiler leaving at 140-160 °C has a dry, invisible plume that disperses quickly. A condensing boiler leaving at 50-60 °C is at or below its dew point, and the plume is a visible white cloud of condensed water that can travel 30-50 m and stain a neighbouring facade. That is not a fault, but it is a planning matter.

The material has to suit the duty. Mild steel is adequate for dry gas above the dew point; below it, stainless or a plastic-lined stack is needed, with a drain at the base and a fall in the flue duct so condensate runs to the drain rather than back into the boiler. A brick chimney serving a condensing boiler suffers acid attack on the mortar unless lined, and the top courses fail first.

Sampling, access and inspection

A stack is also a measurement point. Sampling ports for oxygen, CO and NOx should sit in a straight section, at least half a diameter upstream and one and a half diameters downstream of any bend or transition, with a platform or a safe ladder access and a 50 mm socket at each port. A stack without ports means emissions can only be estimated, and the first test costs a scaffold and a shutdown.

Inspection needs a corrosion allowance at the base, a drain and access to the guy wires. Stainless liners need expansion joints not anchored rigidly at both ends. The table gives typical figures for packaged gas boilers at 12 m/s and a stack 1.5 times the boiler house height.

Boiler capacity Flue gas at 160 °C Stack bore Height above roof
1 t/h 1,700 m³/h 250 mm 4-6 m
2 t/h 3,300 m³/h 320 mm 5-8 m
4 t/h 6,600 m³/h 450 mm 6-10 m
6 t/h 9,800 m³/h 550 mm 8-12 m
10 t/h 16,400 m³/h 700 mm 10-15 m

These are starting points, not a design. The height column assumes a boiler house of 6-8 m and no obstruction within 30 m; add height where the building is taller, windows or intakes are nearby, or the authority sets more. The diameter assumes one boiler at full load; a shared stack needs the combined flow, and three boilers are easier to balance with individual flues inside a common shell.

The final check is a dispersion calculation for the worst case: minimum wind speed, stable atmosphere, full load and the nearest sensitive receptor. That turns a rule of thumb into a defensible height, and it is cheap against rebuilding a stack that drew complaints in its first winter.