View detailsA 6 t/h biomass boiler burning wood waste and paper rejects supplies corrugator and drying steam in Surabaya, with an economizer and multi-cyclone dust collector.

The mill makes corrugated board and boxes in Surabaya and generates a steady stream of trim, reject board and pallet wood. Disposal was costing money. A 6 t/h biomass boiler at 1.25 MPa now burns that stream and supplies the corrugator’s preheaters, the starch kitchen and the drying section.
The load is typical of a packaging plant: about 4 t/h for most of the shift, rising to 5.5-6 t/h when two corrugators run and the starch kitchen heats. Steam pressure has to stay within 1.15-1.25 MPa because the corrugator’s pressure control is sensitive to swings.
Trim and reject board are light, bulky and variable. The boiler is a DZL chain-grate unit with a 6 t/h rating at 1.25 MPa, but the fuel yard does the real work: a shredder reduces board to 50 mm pieces, a magnetic separator pulls staples and wire, and a covered store keeps moisture under 25%. Without that preparation the chain grate would run unevenly and the furnace would pulse.
The mix is roughly 70% shredded board and 30% wood waste, with an LHV around 12-14 MJ/kg. At 6 t/h the fuel rate is about 1.35 t/h, so the mill’s own waste covers the steam demand with a surplus in most weeks.
| Item | Value |
|---|---|
| Rated evaporation | 6 t/h |
| Pressure / temperature | 1.25 MPa / 194 °C |
| Fuel | shredded board, trim, wood waste |
| Fuel LHV | 12-14 MJ/kg |
| Full-load fuel rate | about 1.35 t/h |
| Dust collection | multi-cyclone plus bag filter |
The mill is inside an industrial estate with housing within a kilometre, so particulate control was a condition of the permit. Flue gas passes a multi-cyclone for the coarse fly ash and then a pulse-jet bag filter, holding outlet dust below 30 mg/Nm3. The stack is 18 m, sized on the estate’s dispersion requirement rather than on the boiler.
Bottom ash goes to a local block maker. Fly ash from the bag filter is collected dry and also sold. Neither stream is hazardous, but both are dusty, so the ash house is enclosed and the conveyors are covered.
The boiler was erected in six weeks and commissioned in nine days. The first week of running exposed one control problem: the grate speed was tied to steam pressure alone, so a sudden drop in load slowed the bed and the fire nearly died. The fix was a cascade loop that holds the bed at a minimum grate speed and lets the ID fan and feedwater control absorb small load changes. After that the unit has run at 4-5.5 t/h with steam pressure inside 0.05 MPa.
External links open the publisher’s website and are provided for background reading.
Yes, in a chain-grate furnace with a bag filter. Ink and tape add minor emissions but the bigger issue is staples and wire, which a magnetic separator ahead of the shredder removes.
About 1.3-1.4 t/h at full load on 12-14 MJ/kg fuel, or roughly 30 t a day over a 22-hour run.